Beacon 110

Single Channel Wall Mount Controller

 
 
The Beacon 110 is gas detection simplified.

The Beacon 110 is a powerful, low cost fixed system controller for one point of gas detection. It is microprocessor controlled, versatile, simple to install and operate, and priced to be the industry's best value single gas detection controller. It is capable of accepting RKI sensors directly for LEL level combustibles, Oxygen, Hydrogen Sulfide, or Carbon Monoxide. The Beacon 110 can also accept any 4-20 mA transmitter (2 or 3 wire, 24 VDC). Sensors can be mounted directly at the Beacon 110 housing, or can be wired remote from the controller.

The 10 amp rated relays are strong enough to directly power external alarms and horns. The digital display has backlighting and simultaneous readout of the gas type and concentration.

The Beacon 110 is also housed in a NEMA 4X rated case for a weather tight seal. This case design complies with lock out / tag out standards and can be fully secured. An external reset switch allows the alarm to be silenced from outside of the controller housing. The Beacon 110 ships complete with a wall mounting kit for easy installation.

RKI offers the industry's widest selection of standard and toxic gas detection sensors, which can be utilized with the Beacon 110, providing gas monitoring protection for almost any application.

Features

  • Low cost versatile solution
  • Compact, weatherproof, NEMA 4X enclosure
  • 115/220 VAC or 24 VDC operation
  • Long life sensors (2+ years typical)
  • Accepts RKI LEL/O2/H2S/CO direct connect sensors
  • Accepts any 4-20 mA transmitter
  • Audible alarm with reset button
  • Two programmable alarm levels
  • Built-in trouble alarm with relay
  • Relay rating 10 amps, form C
  • Provides 4-20 mA output
 
 
Applications
  • Petrochemical plants
  • Refineries
  • Water & wastewater treatment pants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • HVAC
 

Specification

Physical


Dimensions Height: 8.5" 216 mm
Width 7.0" 178 mm
Depth 4.3" 109 mm
Enclosure Wall mounting grey polycarbonate with hinged cover.
Conduit
Connection
3/4" NPT conduit hubs, 2 provided.
1 for sensor wiring
1 for power & relay wiring
Wiring
Termination
Screw type terminal block 14 gauge max.
Power
Universal 115 VAC & 220 VAC, or 24 VDC nominal, battery backup option available
Controls
3 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset


Environmental


Operating Temp -4°F to 122°F (-20°C to 50°C)
Storage Temp -4°F to 158°F (-20°C to 70°C)
Relative
Humidity
0 - 100% RH
Enclosure
Rating
NEMA-4X enclosure, waterproof, chemical, and weather resistant.


Inputs


Direct Wired
Sensors
LEL
Oxygen
Carbon Monoxide
Hydrogen Sulfide
Remote amp not required for less than 500 feet.
4-20 mA Sensors Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. (See list of detectable gases.) Wiring distances up to 5000 feet
Sampling Methods Diffusion and sample draw heads available.


Outputs


Relays 3 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarms and 1 trouble relay. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off
4-20 mA Signal output, 4-20 mA (maximum load impedance 500 ohms), per channel
24 VDC 24 VDC (400 mA max) output provided to operate sample drawing adapters or other accessories
Display 2 x 8 Alphanumeric display with backlighting.
Audible Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail
Visual 3 LED’s on the front cover for alarm status indication, and malfunction




 
 
 
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed.
Ammonia (NH3)
0 - 75.0 ppm
Arsine (AsH3 ) 0 - 0.20 ppm
Boron Trichloride (BCl3) 0 - 15.0 ppm
Carbon Dioxide (CO2) 0 - 1.0 %
Carbon Monoxide (CO) 0 - 300 ppm
Chlorine (Cl2) 0 - 3.0 ppm
Chlorine Dioxide (ClO2) 0 - 1.00 ppm
Chlorine Trifluoride (ClF3) 0 - 1.00 ppm
Combustibles 0 -100% LEL
Diborane (B2H6) 0 - 30.0 ppm
Fluorine (F2) 0 - 6.0 ppm
Hydrogen (H2) 0 - 2000 ppm
Hydrogen Chloride (HCl) 0 - 15.0 ppm
Hydrogen Fluoride (HF) 0 - 9.0 ppm
Hydrogen Sulfide (H2S) 0 -100.0 ppm
Nitric Oxide (NO) 0 -100.0 ppm
Nitrogen Dioxide (NO2) 0 - 15.0 ppm
Nitrogen Trifluoride (NF3) 0 - 30.0 ppm
Oxygen (O2) 0 - 25.0 %
Ozone (O3) 0 - 1.0 ppm
Phosphine (PH3) 0 - 1.0 ppm
Silane (SiH4) 0 - 15.0 ppm
Sulfur Dioxide (SO2) 0 - 30.0 ppm
TEOS (Si(OC2H5)4) 0 -15/30 ppm
 
 
 
 
 
 
 
 
 
 